| Model | 3F88L-160 | 3F88L-162 |
|---|---|---|
| Supply voltage | 100 to 240 VAC, 50/60 Hz | |
| Allowable supply voltage | 85 to 264 VAC | |
| Power consumption | 27 VA max. | |
| Inrush current | 40 A at 10 ms max. | |
| I/O power supply | 145 mA at 24 VDC | |
| Allowable I/O supply voltage | 20.4 to 26.4 VDC | |
| Insulation resistance | 20 MΩ min. between all external AC power supply terminals and the protective ground terminal (at 500 VDC) * | |
| Dielectric strength | 2,300 VAC at 50/60 Hz for 1 min between all external AC power supply terminals and the protective ground
terminal (leakage current: 10 mA max.) * |
|
| Noise immunity | IEC 61000-4-4: 2 kV power line | |
| Vibration resistance | Conforms to JIS C0911: 10 to 57 Hz with 0.075-mm single amplitude 80 min each in X, Y, and Z directions,
57 to 150 Hz at 9.8-m/s2 acceleration (sweeps: 8 min × 10 sweeps = 80 min total) |
|
| Shock resistance | Conforms to JIS C0912: 147 m/s2 three times each in X, Y, and Z directions | |
| Ambient operating temperature | 0 to 55°C | |
| Ambient operating humidity | 10% to 90% (with no condensation) | |
| Ambient operating atmosphere | No corrosive gases | |
| Ambient storage temperature | -20 to 75°C | |
| Terminals screw size | Power supply input: M3.5, control I/O: M3 | |
| Momentary power interruption
detection time |
Does not detect momentary power interruptions lasting less than 15 ms. | |
| Dimensions | 110 × 100 × 82.5 mm (W × H × D) | |
| Weight | 1 kg max. | |
| Structure | Mounted inside panel | |
| Mounting method | Screw mounting (two M4 screws) or DIN Track mounting | |