Page top

New

K3CV

IO-Link AD 轉換器

K3CV

將類比訊號轉換為 IO-Link,可有效減少控制面板與設備之間的配線

General specifications

Item Description
Rated input voltage 24 VDC
Operating voltage range 18 to 30 VDC, including ripple (p-p) of 10%
External power supply
(Analog input type)
24 VDC: Linked to input voltage
Maximum load current 100 mA
Current consumption 8 mA (maximum 108 mA when powered externally: analog input type)
Ambient operating temperature -40 to 70°C (with no condensation or freezing)
Ambient operating humidity Relative humidity ≤ 85%
Storage temperature -40 to 85°C (with no condensation or freezing)
Storage humidity Relative humidity ≤ 85%
Vibration resistance 10 to 55 Hz double amplitude 1.5 mm 2h in each of X, Y, and Z directions
Shock resistance 500 m/s2 Three times in each of X, Y, and Z directions
Weight 30 g
Material PA
Protection circuit Reverse polarity protection
Protection structure
(dust-proof, waterproof)
IP67, UL Standard Type 1 Certification, IP30 (When cables are not connected)
Insert/Remove Durability 50 cycles
Cable length
(from master to convertor)
≤ 20 m
Cable length
(from master to sensor)
≤ 30 m and TC of 100 Ω or less and Pt of 10 Ω or less
Conformity standards cULus: Listed (UL61010-1/UL61010-2-201/CSA-C22.2 No.61010-1/
CSA-C22.2 No.61010-2-201)
CE/UKCA: EN61131-2
RCM: EN61000-6-4
IO-Link conformance
Environment UL Certification Temperature: 70°C
Indoor Use
Altitude: 2,000 m max.
Pollution Degree: 3
EMC Immunity Level: Zone B
Power Supply Class2, LPS, LIM and SELV or PELV, PS2 and ES1

Input specifications

Analog input type

Item Description
Sampling rate Switchable between 50 ms (default) and 5 ms
Influence of temperature ±1% FS ±1 digit or less
Influence of voltage
Installation influence
Influence of EMS
Instruction
range
K3CV-1ADIA-IL3 Specification 4 to 20 mA
Instruction range 3.00 to 21.00 mA
Input resistance 150 Ω or lower
K3CV-1ADIB-IL3 Specification 0 to 20 mA
Instruction range -1.00 to 21.00 mA
Input resistance 150 Ω or lower
K3CV-1ADVA-IL3 Specification 0 to 10 V
Instruction range -1.00 to 11.00 V
Input resistance 1 MΩ or higher
K3CV-1ADVB-IL3 Specification -10 to 10 V
Instruction range -11.00 to 11.00 V
Input resistance 1 MΩ or higher
Instruction accuracy (ambient temperature: 23°C) ±0.2% FS ±1 digit or less

TC input type

Item Description
Sampling period Switchable between 50 ms (default) and 10 ms
Influence of temperature (The greater of ±1% of the instruction value or ±4°C)
±1 digits or fewer
Influence of voltage
Installation influence
Influence of EMS
Influence of signal source resistance 0.1°C/Ω or less
Thermocouple type K thermocouple
Cold junction compensation method Switchable between ON (default) and OFF
Instruction
range
K3CV-1TCKA-IL3 Specification -20 to 500°C/0 to 900°F
Instruction range -40.0 to 520.0°C/-40.0 to 940.0°F
Instruction accuracy (ambient temperature: 23°C) (The greater of ±1% of the instruction value or ±2°C)
±1 digits or fewer

Pt input type

Item Description
Sampling period Switchable between 50 ms (default) and 10 ms
Influence of temperature (The greater of ±1% of the instruction value or ±2°C)
±1 digits or fewer
Influence of voltage
Installation influence
Influence of EMS
Influence of signal source resistance 0.1°C/Ω or less
Compatible sensor Pt100
Connection method 3-line
Sensor current 250 μA
Instruction
range
K3CV-1PTPA-IL3 Specification -200 to 500°C/-300 to 900°F
Instruction range -220.0 to 520.0°C/-340.0°C to 940.0°F
Instruction accuracy (ambient temperature: 23°C) (The greater of ±0.2% of the instruction value or ±0.8°C)
±1 digits or fewer

IO-Link Specifications

Item Description
IO-Link device Package 2024 compatible
Baud rate COM3: 230.4 kbps (Fixed)
Device profile Common Profile, Locator
Minimum cycle time COM3: 2.0 ms
Data length 16 bit
Port class Class A
Process data 16 bit
Conversion principle ADC ∠Σ
ADC resolution 16 bit
Control output Switchable between physical quantity (default) and count value
Moving average filter 0 (default), 2, 4, 8, 16, 32: Switchable

Please contact your OMRON sales representative regarding the IO-Link setup file (IODD file).